252kV,550kV Gas Insulated Switchgear (GIS)

252kV,550kV Gas Insulated Switchgear (GIS)
Product Detailed
comply with IEC 62271-203

Parameters:

Rated voltage:252kV,550kV.

Rated current:2000-6300A

Rated breaking current,3s:50kA

Features:

Compact design,three phases Busbar in common tank,save installation area

Rated breaking current 50kA for the circuit breakers.

High operation reliability,less maintenance.

High anti-seismic capability.

The sealing system which has proven extremely reliable over years of utilizaiton.

Meet customer requirements by modular design.

Rated voltage  kV252550
Rated frequency  Hz50/60
Rated current  A40006300
Rated short-circuit breaking current  kA5063
Rated short-time withstand current (r.m.s)  kA5063
Rated duration of short-circuit  s33
Rated peak withstand current  kA125171
Rated short-duration power-frequency withstand voltage (1 min r.m.s) Phase-to-earthkV460740
 Across the insolating distancekV460+145740+315
Rated lightning impulse withstand voltage(peak) Phase-to-earthkV10501675
 Across the insolating distancekV1050+261675+450
SF6 gas pressure at 20°cCircuit breakerRated pressureMPa0.62
Alarm pressureMpa0.58
Lockout pressureMPa0.53
OtherRated pressureMPa0.58
First alarm pressureMPa0.53
Second alarm pressureMPa0.50
Partial discharge at 80% power frequency withstand voltage Total baypC5
 insulatorpC3
The times of Rated short circuit making current (FES)  Times2
Mechanical endurance Circuit breakerTimes10000
 DES/FESTimes5000
Moisture content of SF6 gasCircuit breaker compartmentcommissioningμL/L≤150
operationμL/L≤ 250
Other compartmentcommissioningμL/L≤ 300
operationμL/L≤ 500
Leakage rate of SF6 gas per year   ≤ 0.3%

252kV,550kV Gas Insulated Switchgear (GIS)