Yueqing Pomanique Electric Co., Ltd.
Main products:Insulator,Surge Arrester,Power Transformer,Disconnector,Cutout Fuse
Products
Contact Us
  • Contact Person : Mr. Zhou Benjamin
  • Company Name : Yueqing Pomanique Electric Co., Ltd.
  • Tel : 86-577-62732638
  • Fax : 86-577-62732636
  • Address : Zhejiang,Yueqing,F14, Jun Hao Xuan, Liuchuan Mansion, North Liuqing Road, Yueqing, Zhejiang, China
  • Country/Region : China
  • Zip : 325604

132kV SF6 outdoor circuit breaker

132kV SF6 outdoor circuit breaker
Product Detailed
132kv sf6 circuit breaker: 1)Voltage:126KV,252KV 2)Excellent Breaking capability 3)High reliability

Outdoor Self-energized High-voltage SF6 Circuit Breaker

 

132kv sf6 circuit breaker

 

LW36-126(252)Type LW36-126(252) outdoor self-energized high-voltage SF6 circuit breaker is applicable in the alternating current 50Hz, 110-220kV power system, it can be used as the electrical protective and control device in the power system, it also can be deemed as the tie circuit breaker.

This kind of circuit breaker complies with the regulation of GB1984-89 < Alternating current high-voltage circuit-breakers > and IEC56 < High-voltage alternating current circuit-breakers >.Base on the principle of self-energized arc distinction, by adopting SF6 as the medium for insulation and arc distinction, the circuit breaker is equipped with type CT24 spring operating mechanism which has the advantages of excellent breaking capability, low operating power and high reliability

 

Service and Environmental Condition

Ambient Temperature:-30°C~+40°C

b. Sea-level Altitude:≤1000m, ≤3000m

c. Wind Speed:≤34m/s

d.Diurnal Temperature Variation :≤25°C

e.Illumination Intensity:≤0.1w/cm

f.Monthly Average Relative Temperature:≤90%

g.Seismic Acceleration:Horizontal: ≤0.2g, Vertical: ≤0.1g

h.Ice Thickness:≤10mm

i.Air Pollution Level:Not less than Level III in GB5582

j.Mounting Site:Outdoor

 

Main Technical Parameters

No.

Item

Unit

Parameter

1

Rated voltage

KV

126(252)

2

Rated  power- frequency withstand voltage(1min)

To earthing

KV

230

Across the isolating distance

KV

230+73*

3

Rated lightning impulse withstand voltage

To earthing

KV

550

Across the isolating distance

KV

550+103*

4

Frequency  withstand voltage at SF6 zero gauge pressure(5min)

KV

95KV

5

Rated frequency

Hz

50

6

Rated current

A

2500,3150

7

First pole-to-clear factor

1.5

8

Rated short-circuit breaking current

kA

31.5   40

9

Rated short circuit making current

kA

80    100

10

Rated short - time withstand current

kA

31.5   40

11

Rated peak withstand current

kA

31.5   40

12

Rated Short-circuit Continuing Time

S

3

13

Rated out of phase breaking current

kA

8   10

14

Short-line fault breaking current

90%   75%

15

Rated line-charging making current

A

3.5

16

Rated short-circuit breaking times

Time

20

17

Rated operating sequence

O-0.3S-CO-180-CO

18

Open time

ms

≤40

19

Making time

ms

≤120

20

Breaking time

ms

≤60

21

Close-open time

ms

≥80

22

Closing simultaneity

ms

≤3

23

Opening simultaneity

ms

≤2

24

Closing speed 

m/s

3.0±0.5

25

Opening speed 

m/s

5.0±0.5

26

Main loop resistance 

μΩ

≤40

27

Rated SF6 pressure (22°C gage pressure)

Mpa

0.6

28

Alarm/lock pressure(20°Cgage pressure)

Mpa

0.55/0.50

29

Annual leakage rate of SF6 gas

≤1%

30

Gas moisture content

ppm

≤150

31

Machinery life

time

6000

32

Radio interference level

uv

≤2500

33

Creapage distance

Across the isolating distance

mm

3150,3906

To earthing

mm

3150,3906

34

Filling SF6 Gas quality for each

kg

10

35

CB quality for each

kg

1300

132kV SF6 outdoor circuit breaker



Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.